Differential protection
Table 27. 1Ph High impedance differential protection HZPDIF
Function Range or value Accuracy
Operate voltage (20-400) V
I=U/R
± 1.0% of I
r
Reset ratio >95% -
Maximum continuous power
U>Trip
2
/SeriesResistor ≤200 W
-
Operate time 10 ms typically at 0 to 10 x U
d
-
Reset time 105 ms typically at 10 to 0 x U
d
-
Critical impulse time 2 ms typically at 0 to 10 x U
d
-