IEC140000118-2-en.vsd
IEC140000118 V2 EN-US
Figure 38: Multiple instances of PMUREPORT function block
Figure
39 shows both instances of the PHASORREPORT function blocks. The
instance number is visible in the bottom of each function block. For each instance,
there are four separate PHASORREPOR
T blocks including 32 configurable phasor
channels (8 phasor channels in each PHASORREPORT block). Each phasor channel
can be configured as a 3-phase (symmetrical components positive/negative/zero) or
single-phase phasor (A/B/C).
IEC140000119-2-en.vsd
IEC140000119 V2 EN-US
Figure 39: Multiple instances of PHASORREPORT blocks
Figure
40 shows both instances of ANALOGREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are
three separate ANALOGREPOR
T blocks capable of reporting up to 24 Analog signals
(8 Analog signals in each ANALOGREPORT block). These can include for example
transfer of active and reactive power or reporting the milliampere input signals to the
PDC clients as defined in IEEE C37.118 data frame format.
1MRK 502 071-UUS A Section 6
Wide area measurement system
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 113
Application manual