EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Page 254

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Voltage distribution on faulty lossless serial compensated line from fault point F to the
bus is linearly dependent on distance from the bus, if there is no capacitor included in
scheme (as shown in figure 111). Voltage V
M
measured at the bus is equal to voltage
drop
D V
L
on the faulty line and lags the current I
F
by 90 electrical degrees.
The situation changes with series capacitor included in circuit between the IED point
and the fault position. The fault current I
F
(see figure
111) is increased due to the series
capacitor, generally decreases total impedance between the sources and the fault. The
reactive voltage drop D
V
L
on X
L1
line impedance leads the current by 90 degrees.
Voltage drop DV
C
on series capacitor lags the fault current by 90 degrees. Note that
line impedance X
L1
could be divided into two parts: one between the IED point and the
capacitor and one between the capacitor and the fault position. The resulting voltage
V
M
in IED point is this way proportional to sum of voltage drops on partial
impedances between the IED point and the fault position F, as presented by
( )
M F L1 C
V I j X X= × -
EQUATION1995-ANSI V1 EN-US (Equation 103)
en06000605_ansi.vsd
~
21
XS
X
L1
IF
V
V
M
Source
Fault voltage
Pre -fault voltage
X
C
Source voltage
V
M
With bypassed
capacitor
With inserted
capacitor
F
X
ANSI06000605 V1 EN-US
Figure 110: Voltage inversion on series compensated line
Section 8 1MRK 502 071-UUS A
Impedance protection
248 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual

Table of Contents

Related product manuals