MultPU: The set operate current can be changed by activation of the binary input
MULTPU
to the set factor MultPU.
9.1.3.1 Meshed network without parallel line
M12915-9 v8
The following fault calculations have to be done for three-phase, single-phase-to-
ground and two-phase-to-ground faults. With reference to Figure
168, apply a fault in
B and then calculate the current through-fault phase current I
fB
. The calculation should
be done using the minimum source impedance values for Z
A
and the maximum source
impedance values for Z
B
in order to get the maximum through fault current from A to
B.
~
~
Z
A
Z
B
Z
L
A B
IED
I
fB
Fault
ANSI09000022-1-en.vsd
ANSI09000022 V1 EN-US
Figure 168: Through fault current from A to B: I
fB
Then a fault in A has to be applied and the through fault current I
fA
has to be
calculated, Figure
169. In order to get the maximum through fault current, the
minimum value for Z
B
and the maximum value for Z
A
have to be considered.
1MRK 502 071-UUS A Section 9
Current protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 343
Application manual