EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Page 472

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
overvoltage protection or a residual differential protection. These protection schemes
are simple and have served well during many years. However, at best these schemes
protect only 95% of the stator winding. They leave 5% at the neutral end unprotected.
Under unfavorable conditions the blind zone may extend to 20% from the neutral.
Some dif
ferent ground fault protection solutions are shown in figure
213 and
figure 214.
Generator unit transformer
+
3V
0
ANSI06000317_3_en.vsd
ANSI06000317 V3 EN-US
Figure 213: Broken delta voltage transformer measurement of 3V
0
voltage
Alternatively zero sequence current can be measured as shown in fig
215
Generator unit transformer
- V
0
+
ANSI06000318_3_en.vsd
ANSI06000318 V3 EN-US
Figure 214: Neutral point voltage transformer measurement of neutral point voltage
(that is V
0
voltage)
Section 10 1MRK 502 071-UUS A
Voltage protection
466 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual

Table of Contents

Related product manuals