en 05000118_ ansi. vsd
SCSWI
SELECTED
RES_ EXT
+
IED
BI
BO
IED
BI
BO
OR
Other SCSWI in the bay
ANSI05000118 V2 EN-US
Figure 239: Application principles for reservation with external wiring
The solution in Figure
239 can also be realized over the station bus according to the
application example in Figure 240. The solutions in Figure 239 and Figure 240 do not
have the same high security compared to the solution in Figure 238, but instead have a
higher availability, since no acknowledgment is required.
SCSWI
SELECTED
RES_EXT
IED
IED
OR
Other SCWI in
the bay
Station bus
. . .
SPGAPC
IN
RESGRANT
IntlReceive
. . .
. . .
RESGRANT
IntlReceive
IEC05000178-3-en.vsd
IEC05000178 V3 EN-US
Figure 240: Application principle for an alternative reservation solution
15.2.2 Interaction between modules
M16626-3 v8
A typical bay with apparatus control function consists of a combination of logical
nodes or functions that are described here:
Section 15 1MRK 502 071-UUS A
Control
552 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062