Figure 244: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.
BC_17_OP No bus-coupler connection between busbar WA1 and WA7.
BC_17_CL A bus-coupler connection exists between busbar WA1and WA7.
BC_27_OP No bus-coupler connection between busbar WA2 and WA7.
BC_27_CL A bus-coupler connection exists between busbar WA2 and WA7.
VP_BC_12 The switch status of BC_12 is valid.
VP_BC_17 The switch status of BC_17 is valid.
VP_BC_27 The switch status of BC_27 is valid.
EXDU_BC No transmission error from any bus-coupler bay (BC).
These signals from each bus-coupler bay (ABC_BC) are needed:
Signal
BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA2.
BC17OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 and
WA7.
BC17CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA7.
BC27OPTR No bus-coupler connection through the own bus-coupler between busbar WA2 and
WA7.
BC27CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA2
and WA7.
VPBC12TR The switch status of BC_12 is valid.
VPBC17TR The switch status of BC_17 is valid.
VPBC27TR The switch status of BC_27 is valid.
EXDU_BC No transmission error from the bay that contains the above information.
1MRK 502 071-UUS A Section 15
Control
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 563