Busbar
Protection
Busbar
1
2
2
1
en06000196_ansi.vsd
ANSI06000196 V1 EN-US
Figure 16: Example how to set CT_WyePoint parameters in the IED
For busbar protection, it is possible to set the CT_WyePoint parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT
inputs marked with 1 in Figure
16, set CT_WyePoint
= ToObject, and for all CT inputs
marked with 2 in Figure
16, set CT_WyePoint
= FromObject.
The second solution will be to use all connected bays as reference objects. In that case
for all CT inputs marked with 1 in Figure
16, set CT_WyePoint =
FromObject, and for
all CT inputs marked with 2 in Figure
16, set CT_W
yePoint =
ToObject.
Section 4 1MRK 502 071-UUS A
Analog inputs
72 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual