A
AI 07 (I)
AI 08 (V)
AI 09 (V)
AI 10 (V)
AI
11 (V)
AI 12 (V)
IED
B
C
6.6
3
110
3
kV
V
+3Vo
6.6
3
110
3
kV
V
6.6
3
110
3
kV
V
1
2
4
3
# Not Used
5
ANSI06000601-2-en.vsd
# Not Used
# Not Used
SMAI2
BLOCK
^GRP2_A
^GRP2_B
^GRP2_C
^GRP2N
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
ANSI06000601 V2 EN-US
Figure 28: Open delta connected VT in high impedance grounded power system
1MRK 502 071-UUS A Section 4
Analog inputs
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 91
Application manual