EasyManua.ls Logo

ABB Relion 670 series - Page 177

ABB Relion 670 series
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Station communication, remote end serial
communication and time synchronization
Ordering no #11 Notes and rules
Slot position (front view/rear view)
P30:1/X301
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
P31:1/X311
P31:2/X312
P31:3/X313
P32:2/X322
P32:3/X323
LDCM mode
1)
Available slots in 1/2, 3/4 and 1/1 case with 1
TRM
2)
Available slots in 3/4 and 1/1 case with 2 TRM
No communication board included X X X X X X X X X X X
Ethernet SFP, optical LC connector 1MRK005500-AA K K K K K K
3)
Ethernet SFP, RJ45 connector 1MRK005500-BA P P P P P P
Optical Ethernet module 1MRK002266-EA H
4)
Serial SPA/LON/DNP/IEC 60870-5-103 plastic
interface
1MRK001608-AB L
Serial SPA/LON/DNP/IEC 60870-5-103 plastic/
glass interface
1MRK001608-BB M
Serial SPA/LON/DNP/IEC 60870-5-103 glass
interface
1MRK001608-CB N
Galvanic RS485 communication module 1MRK002309-AA G G G
Optical short range, LDCM 820 nm 1MRK002122-AB A A A A A A
5)
,
6)
,
7)
,
8)
Optical medium range, LDCM 1310 nm 1MRK002311-AA B B B B B B
Optical long range, LDCM 1550 nm C C C C C C
Line data communication, default 64kbps
mode
X
9)
Allow line data communication in 2Mbps mode 1MRK007002-AA Y
GPS time module 1MRK002282-AB S S S S
IRIG-B time synchronization module, with PPS 1MRK002305-AA F F F F
Selection for
position #11
1) The maximum number and type of LDCM modules supported depend on the total amount of I/O and communication modules in the IED.
2) Max 2 LDCM in 1/2 case
3) Ethernet SFP is basic in P30:1. P30:6:1 and P30:6:2 require the Optical Ethernet module in P30:6.
4) When OEM is ordered in combination with 2 or 4 LDCMs in redundant mode, it is required to order RED as a customized product.
5) For RED670 A42, B42 and C42, one LDCM is required in P30:5.
6) For RED670 B33, two LDCMs are required in P30:5 and P31:2.
7) For RED670-B33, LT3CPDIF included as Basic. One of the following (LT6CPDIF/L6CPDIF/L3CPDIF) as optional.
8) Max 4 LDCMs can be ordered. Always place LDCM modules on the same board to support redundant communication: P30:5, P30:6, P31:2, P31:3 or P32:2 and P32:3.
9) For A42/B42/C42, only 2Mbps is allowed. For B33, select either 64kbps or 2Mbps; default is 64kbps.
Line differential protection RED670
1MRK 505 379-BEN N
Version 2.2
Hitachi Power Grids 177
© Copyright 2017 Hitachi Power Grids. All rights reserved

Other manuals for ABB Relion 670 series