EasyManua.ls Logo

ABB Relion 670 series - Page 80

ABB Relion 670 series
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 37. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 2 Mbits/s communication
Function Range or value Accuracy
Minimum operate current (20-200)% of
IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
SlopeSection2 (10.0-50.0)% -
SlopeSection3 (30.0-100.0)% -
EndSection 1 (20–150)% of
IBase
-
EndSection 2 (100–1000)% of
IBase
-
Unrestrained limit function (100–5000)% of
IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Second harmonic blocking (5.0–100.0)% of fundamental ±1.0% of I
r
Note: fundamental magnitude = 100% of I
r
Fifth harmonic blocking (5.0–100.0)% of fundamental ±3.0% of I
r
Note: fundamental magnitude = 100% of I
r
*Inverse characteristics, see table
196,198 and table 200
16 curve types See table 196,198 and table 200
Critical impulse time 2 ms typically at 0 to 10 x I
dMin
-
Charging current compensation On/Off -
LT3CPDIF and LT6CPDIF (With in-zone transformer enabled and tIdMinHigh set to 0) :
*Operate time, restrained function at
0 to 10 x I
dMin
Min. = 25 ms
Max. = 40 ms
-
*Reset time, restrained function at 10
x I
dMin
to 0
Min. = 5 ms
Max. = 20 ms
-
*Operate time, unrestrained function
at 0 to 10 x I
dUnre
Min. = 5 ms
Max. = 20 ms
-
*Reset time, unrestrained function at
10 x I
dUnre
to 0
Min. = 15 ms
Max. = 35 ms
-
**Operate time, unrestrained negative
sequence function
Min. = 10 ms
Max. = 25 ms
-
**Reset time, unrestrained negative
sequence function
Min. = 10 ms
Max. = 30 ms
-
L3CPDIF and L6CPDIF (With tIdMinHigh set to 0):
*Operate time, restrained function at
0 to 10 x I
dMin
Min. = 10 ms
Max. = 20 ms
-
*Reset time, restrained function at 10
x I
dMin
to 0
Min. = 15 ms
Max. = 30 ms
-
*Operate time, unrestrained function
at 0 to 10 x I
d
Min. = 5 ms
Max. = 20 ms
-
*Reset time, unrestrained function at
10 x I
dUnre
to 0
Min. = 15 ms
Max. = 35 ms
-
Line differential protection RED670
1MRK 505 379-BEN N
Version 2.2
80 Hitachi Power Grids
© Copyright 2017 Hitachi Power Grids. All rights reserved

Other manuals for ABB Relion 670 series

Related product manuals