Test point Reach Set value Comments
10 X 0.5 x X1
set
Exact –0.5 x R1
set
x tan(ArgNegRes=30°)
R –0.23 x X1
set
11 X 0.8 x X1
set
Exact –0.5 x R1
set
x tan(ArgNegRes=30°)
R –0.37 x X1
set
12 X 0.5 x X1
set
R 0.5 x R1
set
13 X 0
R 0.5 x RFPPZx
Table is used in conjunction with figure .
(2 x X1set+X0set)/3
R
X
(
Ω
/loop)
50%
80%
1
2
3
4
5
6
7
8
9
10
11
50% of RFPEZx
25% of RFPEZx
RFPG
12
ANSI05000369-3-en.vsdx
13
ArgLd
alt. 80% of
RFPG (Load
encroachment)
ArgDir
ANSI05000369 V3 EN-US
Figure 38: Distance protection characteristic with test points for phase-to-ground measurements
Table is used in conjunction with figure .
Table 33: Test points for phase-to-ground C-G (Ohm/Loop)
Test point
Reach Value Comments
1 X (2 x X1
set
+X0
set
)/3
R 0
2 X (2 x X1
set
+ X0
set
)/3
R 2 x R1
set
+ R0
set
)/3
3 X 0.8 x (2 x X1
set
+ X0
set
)/3
R 0.8 x (2 x R1
set
+ R0
set
)/3
+RFPGZx
set
Table continues on next page
Section 11 1MRK 504 165-UUS Rev. J
Testing functionality by secondary injection
130 Transformer protection RET670
Commissioning manual