EasyManua.ls Logo

ABB Relion 670 series - Page 153

ABB Relion 670 series
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
and the voltages that are related to them:
V Z I R X I
t FwdZ FwdZ t FwdR FwdX t,
. . .= × = + × = + × =
2 2 2 2
0 078 0 565 20918 0 5700 20918 11931× = V
EQUATION14052 V1 EN-US (Equation 16)
V Z I R X I
t RvsZ RvsZ t RvsR RvsX t,
. . .= × = + × = + × =
2 2 2 2
0 003 0 282 20918 0 2822 20918 5899× = V
EQUATION14053 V1 EN-US (Equation 17)
The previous calculations are in primary values. They are transferred to secondary values to perform
injections by a test set. Primary values are transferred to secondary values by taking into account the CT
ratio and the VT ratio (respectively 9000/1 A and 13.8/0.1 kV in the example).
The magnitude of the secondary voltages, that are related to the points RE and SE of the R-X plane,
needs to be checked.
RE (R
FwdR
, X
FwdX
):
V V
V
V
V
t FwdZs t FwdZ
VT s
VT p
, ,
,
,
.
.
.= × = × =11931
0 1
13 8
86 45
EQUATION14054 V1 EN-US (Equation 18)
SE (R
RvsR
, X
RvsX
):
V V
V
V
V
t RvsZs t RvsZ
VT s
VT p
, ,
,
,
.
.
.= × = × =5899
0 1
13 8
42 75
EQUATION14055 V1 EN-US (Equation 19)
The tests, which are described in this section, may require voltages that have magnitude equal to 110%
of the previous values. The continuous permissive overload voltage of the protection voltage channels of
the TRM module is 420 V; so the previous voltages may be applied to the analog channels of the IED
continuously. Limitations may be related to the available test set; the current I
t
was calculated by using a
factor 2.5 (instead of the maximum value 4) in order to reduce the magnitude of the test voltage for the
points RE and SE.
Test sets usually do not have a feature to simulate a real network during a power swing and apply the
related analog quantities at the terminal of the generator. The scope of the present test is not a
simulation of a real network. Voltages and currents are supplied in order to measure an impedance that
changes in the time and traverses the plane R-X and, in particular, the area inside the lens characteristic.
The test may be performed by applying:
Symmetric three-phase voltage at 50 Hz. The magnitude depends on the point of the characteristic
that needs to be verified. The following three main points of the line segment SE-RE need to be
checked:
the point RE (R
FwdR
, X
FwdX
)
a point which is related to the parameter ReachZ1 (boundary between zone 1 and zone 2)
the point SE (R
RvsR
, X
RvsX
)
The phase angle of the test voltages is equal to:
arctan (ForwardX/ForwardR) for tests in the quadrant 1 and 2 of the R-X plane
arctan (ReverseX/ReverseR) -180° for tests in the quadrant 3 and 4 of the R-X plane
1MRK 504 165-UUS Rev. J Section 11
Testing functionality by secondary injection
Transformer protection RET670 147
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals