Steady voltage and current are applied in order to get a steady high impedance, that is a point in the
plane R-X which is far away from the lens characteristic. Define the following three-phase
symmetrical quantities (the phase angle is related to phase L1):
V V
V
V
V
ts t RvsZ
VT s
VT p
= × × = × × =0 9 0 9 5899
0 1
13 8
38 47. .
.
.
.
,
,
,
EQUATION14067 V1 EN-US (Equation 65)
29.60
arctan 180 arctan 180 90.56
0.29
ts
ReverseX
V
ReverseR
Ð = - ° = - ° = - °
æ ö æ ö
ç ÷ ç ÷
è ø è ø
EQUATION14068 V1 EN-US (Equation 66)
frequency of V
ts
= 50 Hz
I
50s
= 0 A
I
tfs
= 0 A
• State 2: main test step.
Define the following three-phase symmetrical quantities (the phase angle is related to phase L1):
V V
V
V
V
ts t RvsZ
VT s
VT p
= × × = × × =0 9 0 9 5899
0 1
13 8
38 47. .
.
.
.
,
,
,
EQUATION14067 V1 EN-US (Equation 67)
29.60
arctan 180 arctan 180 90.56
0.29
ts
ReverseX
V
ReverseR
Ð = - ° = - ° = - °
æ ö æ ö
ç ÷ ç ÷
è ø è ø
EQUATION14068 V1 EN-US (Equation 68)
frequency of V
ts
= 50 Hz
I I
I
I
A
s
CTs
CTp
50 50
10459
1
9000
1 162= × = × = .
EQUATION14059 V1 EN-US (Equation 69)
∠I
50s
= 0º
frequency of I
50s
= 50 Hz
It I
I
I
A
fs
CTs
CTp
tf= × = × =10459
1
9000
1 162.
EQUATION14062 V1 EN-US (Equation 70)
∠I
tfs
= 180º
frequency of I
tfs
= 50.5 Hz
Expected result: start of the protection function and trip in zone 1 when trip conditions are fulfilled.
The trajectory of the impedance does not enter the lens characteristic
GUID-189FECED-12A7-4A41-BCCF-D93C0FF9FA41 v1
Preliminary steady state test at 50 Hz
GUID-448D5357-6CC2-438E-83CA-25FD381B7DFF v1
• Go to Main menu /Test /Function status /Impedance protection /OutOfStep(78,Ucos) /
OOSPPAM(78,Ucos):1 /Outputs to check the available service values of the function block
OOSPPAM.
• Apply the following three-phase symmetrical quantities (the phase angle is related to phase L1):
1MRK 504 165-UUS Rev. J Section 11
Testing functionality by secondary injection
Transformer protection RET670 157
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved