2.4. Set the Device ID Code in PMU Connection Tester per PMU Data Stream ID Number
(IDCODE). The PMU Data Stream ID Number is a user assigned ID number (1-65534) for
each data stream sent out from the PMU and it is defined under parameter
PMUdataStreamIDCODE. ( Main menu /Configuration /Communication /Station
communication /phasor measurement /PMU Report /PMUREPORT:1 )
2.5. Make sure that the Configure Alternate Command Channel is set as Not Defined. The
Configure Alternate Command Channel is used to configure a TCP channel to control the
UDP data communication and transfer the header, configuration and command frames.
2.6. Continue to the section
Verifying the IEEE C37.118/1344 TCP communication.
3. Set the Connection Parameters on PMU Connection Tester for UDP communication according to
the PMU configuration.
IEC140000136 V1 EN-US
3.1. Set the Local Port to UDP destination port defined in the PMU under the parameter
UDPDestPort1 (Default value: 8910).
3.2. Click the Configure Alternate Command Channel to configure the TCP channel. A new
window will pop up. A TCP channel needs to be configured in order to control the UDP data
communicatiuon and transfer the header, configuration and command frames.
IEC140000137 V1 EN-US
3.3. Set the Host IP as the PMU IP address configured for the port in use. Here the LANAB:1
IPAddress (192.168.1.10) is set.
1MRK 504 165-UUS Rev. J Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Transformer protection RET670 71
Commissioning manual