IEC140000139-1-en.vsd
IEC140000139 V1 EN-US
Figure 11: Graphic view over streaming synchrophasor data
Open the drop-down menu in the Command field. There is a list of commands that can be sent from
the client (PMU Connection Tester) to the PMU. Try different commands and make sure that the
PMU is receiving and responding to them.
1MRK 504 165-UUS Rev. J Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Transformer protection RET670 73
Commissioning manual