IEC15000024 V1 EN-US
The Signal Monitoring menu changes and indicates the forcing values that can be edited.
IEC15000025 V1 EN-US
5. Select and edit the values.
6. Click Acknowledge and send.
IEC15000026 V1 EN-US
This commits the values to the IED and exits the editing session.
7. Click Cancel to abort the changes and revert back to actual IED values.
IEC15000032 V1 EN-US
Regardless if the forcing changes are commited or canceled, the forcing is still active.
To force more signals, click the button Start editing signal value for forcing again.
1MRK 504 165-UUS Rev. J Section 10
Testing IED operation
Transformer protection RET670 91
Commissioning manual