Name Type Description
COUNT3P1 INTEGER Counting the number of three-phase reclosing shot 1
COUNT3P2 INTEGER Counting the number of three-phase reclosing shot 2
COUNT3P3 INTEGER Counting the number of three-phase reclosing shot 3
COUNT3P4 INTEGER Counting the number of three-phase reclosing shot 4
COUNT3P5 INTEGER Counting the number of three-phase reclosing shot 5
COUNTAR INTEGER Counting total number of reclosing shots
MODE INTEGER Integer output for reclosing mode
12.2.5 Setting parameters
Table 322: SMBRREC (79) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
External ctrl
Enabled
- - External ctrl Off, ExternalCtrl, On
ARMode 3 phase
1/2/3ph
1/2ph
1ph+1*2ph
1/2ph+1*3ph
1ph+1*2/3ph
- - 1/2/3ph The AR mode selection e.g. 3ph, 1/3ph
t1 1Ph 0.000 - 60.000 s 0.001 1.000 Open time for shot 1, single-phase
t1 3Ph 0.000 - 60.000 s 0.001 6.000 Open time for shot 1, delayed reclosing 3ph
t1 3PhHS 0.000 - 60.000 s 0.001 0.400 Open time for shot 1, high speed reclosing 3ph
tReset 0.00 - 6000.00 s 0.01 60.00 Duration of the reset time
tSync 0.00 - 6000.00 s 0.01 30.00 Maximum wait time for synchronism-check OK
tTrip 0.000 - 60.000 s 0.001 0.200 Maximum trip pulse duration
tPulse 0.000 - 60.000 s 0.001 0.200 Duration of the circuit breaker closing pulse
tCBClosedMin 0.00 - 6000.00 s 0.01 5.00 Minimum time that CB must be closed before
new sequence allows
tUnsucCl 0.00 - 6000.00 s 0.01 30.00 Wait time for CB before indicating
Unsuccessful/Successful
Priority None
Low
High
- - None Priority selection between adjacent terminals
None/Low/High
tWaitForMaster 0.00 - 6000.00 s 0.01 60.00 Maximum wait time for release from Master
Section 12 1MRK505222-UUS C
Control
650
Technical reference manual