IEC16000099 V1 EN-US
Figure 79: PCM600: Options dialog window
The “IEC 61850 configuration engineering mode enabled” option
under Tools/Options/IEC 61850 Configuration/Enginneering tab
has to be checked to get the option above enabled.
8.4.3 Making GOOSE connections in the application
configuration tool
GUID-2847BE10-3519-4EC8-97A2-A5A11A9ADCEC v1
GOOSE connections via Easy GOOSE can be created in two ways:
• via GOOSE receive functions
• via normal function blocks.
8.4.3.1 Create GOOSE connections via GOOSE receive functions
GUID-F16104FF-C8BB-4455-807E-336E1AA09124 v1
1. Select and right click on the input signal of the GOOSE Receive function,
point to “Connect” and select the “GOOSE” option.
Section 8 1MRK 511 398-UEN C
IEC 61850 communication engineering
120 670 series 2.2 IEC
Engineering manual