For more information on SCL configuration data attributes, see Section "User
interface".
In this case, the GOOSE connection will be added as shown in Figure 82
below.
IEC16000175 V1 EN-US
Figure 82: ACT: GOOSE configuration on Receiver IED side (left) and
Sender IED (right) side
8.4.3.2 Create GOOSE connections via normal function blocks
GUID-573EF145-F558-4A2C-9F0E-B3614B2ECD29 v1
1. Select and right click on the input signal of a normal function block, point to
“Connect” and select the “GOOSE” option.
IEC16000176 V1 EN-US
Figure 83: PCM600: GOOSE option in ACT
The “Connect to GOOSE” dialog window opens. For detailed information
about the “Connect to GOOSE” dialog window refer to Section "User
interface".
2. Under Sender IEDs section, select needed data attribute in the Application
configuration tab
3. Click on the “Connect” button.
The “Select GOOSE Block and Signal” dialog window opens. For detailed
information about the “Select GOOSE Block and Signal” dialog refer to
Section
"User interface".
Section 8 1MRK 511 398-UEN C
IEC 61850 communication engineering
122 670 series 2.2 IEC
Engineering manual