The data set for GOOSE contains signals on the data attribute
or FCDA levels. The latter is also known as structured
GOOSE.
Data for one signal can only be included in one GOOSE data
set. The data set for GOOSE cannot be empty.
4. Create a GOOSE control block and connect it to the GOOSE data set. Check
parameters for GOOSE control block, for eaxample MinTime and MaxTime,
and update as required.
5. Connect the GOOSE control block to receiving IEDs that subscribe GOOSE
data.
6. Export the SCD file.
8.6 Importing SCL files to PCM600
GUID-DA35857B-999B-4533-8148-864B69ECDBCE v2
PCM600 is able to import SCD, ICD and CID files.
8.6.1 Importing SCD files
GUID-93604C46-1A65-4A25-9334-59478FC1C0A0 v6
Procedure to import an SCD file to PCM600:
1. Select the sub-station in the plant structure.
2. Right-click on the sub-station and select Import ...
3. Select the file and start the import.
4. An SCL Import Options window opens to enable you to configure import
handling (see
Figure 87):
Section 8 1MRK 511 398-UEN C
IEC 61850 communication engineering
128 670 series 2.2 IEC
Engineering manual