Section 9 IEC 60870-5-103 communication
engineering
9.1 Engineering in PCM600
GUID-284EB0BA-BC79-4B90-8B78-878BA225479E v7
The Application Configuration tool (ACT) and the Parameter Setting tool (PST) in
PCM600 are used to configure the communication for IEC 60870-5-103 protocol.
1. Add the desired IEC 60870-5-103 function blocks to the application
configuration in the Application Configuration tool.
2. Connect the outputs of desired protection and monitoring function in the
application configuration to the inputs of the corresponding IEC 60870-5-103
function block.
3. Set the function type and desired information number, where an information
number must be supplied, for each IEC 60870-5-103 function block instance
in the Parameter Setting tool.
4. Set the general communication settings for IEC 60870-5-103 and time
synchronization parameters in the Parameter Setting tool.
See the Communication protocol manual for IEC 60870-5-103 for more
information about the IEC 60870-5-103 implementation in the IED series.
9.1.1 Settings for RS485 and optical serial communication
M17109-118 v12
General settings
SPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM optical
serial port while DNP and IEC 60870-5-103 additionally can utilize the RS485
port. A single protocol can be active on a given physical port at any time.
Two different areas in the HMI are used to configure the IEC 60870-5-103
protocol.
1. The port specific IEC 60870-5-103 protocol parameters are configured under:
Main menu/Configuration/Communication/Station Communication/
IEC60870-5-103/
• <config-selector>
• SlaveAddress
• BaudRate
• RevPolarity (optical channel only)
• CycMeasRepTime
• MasterTimeDomain
• TimeSyncMode
1MRK 511 398-UEN C Section 9
IEC 60870-5-103 communication engineering
670 series 2.2 IEC 133
Engineering manual