The mapping status is indicated visually. It can be seen what FPN data attribute is
mapped to what PCM600 internal data attribute and how many FPN data attributes
are mapped to a PCM600 internal data attribute.
Data attribute mapping is complete when all data attributes of the FPN IED, which
are not excluded from the mappings, are mapped with a PCM600 internal data
attribute. The data attribute mapping must be complete in order to be able to write
to IED.
Data attribute mapping is broken if any of the data attributes - FPN or PCM600
internal - that are mapped, does not exist in the SCL database.
When performing data attribute mapping, understand the following visual signs:
Completely mapped
Not mapped
Broken mapping
Partially mapped
Object is excluded from the mappings
All data attributes in the FPN model must be mapped or excluded,
otherwise write to IED fails.
11.4.2.1 Data Attribute Level Mapping
GUID-21AF369A-EF96-4039-BBE4-E925E5A3C488 v2
The IEC 61850 Structure Mapping Tool displays the FPN data attributes and
PCM600 internal data attributes in separate lists. The mapping is done by dragging
and dropping the FPN data attribute onto a PCM600 internal data attribute.
The mapping is removed by right clicking and selecting remove from the context
menu or by clicking the Delete key while the mapping is selected.
IEC17000030-1-en.v sdx
IEC17000030 V1 EN-US
Figure 112: Data attribute level mapping
Section 11 1MRK 511 398-UEN C
Flexible product naming
152 670 series 2.2 IEC
Engineering manual