IEC09000710-3-en.vsd
IEC09000710 V3 EN-US
Figure 14: PCM600: Set up a plant structure
Once a plant structure is built, the name of each level in the structure should be
renamed by the names/identifications used in the grid. Use the right mouse button
to build the plant structure by selecting the elements from the context menu.
Rename the level after insertion using the Rename possibility or the Object
Properties. Figure
14 shows the start of a project with two IEDs placed but still not
renamed.
The plant structure corresponds to the complete grid including the
needed IEDs.
Procedure to build a plant structure:
Right-click on the plant structure, select New and Create from Template ..., or
Right-click on the plant structure, select New, General and select either IED
Group or Substation.
Click View in the menu bar and select Object Types. Select the needed
elements and drag and drop them into the plant structure. Close the window if
it does not close automatically.
4.6.1 IEC 61850 naming conventions to identify an IED
SEMOD58409-38 v10
This section is only valid when the IEC 61850 standard is used for station bus
communication. According to the IEC 61850–6 clause 8.4, the SCL model allows
two kinds of project designation in the object properties.
1MRK 511 398-UEN C Section 4
Setting up a project
670 series 2.2 IEC 45
Engineering manual