1.1. Select Tools/Options....
1.2. In Options/IEC 61850 Configuration, open the Miscellaneous tab.
1.3. Check Allow changing SCL version of an IED configuration.
IEC17000133-1-en.vsdx
1.4. Click OK to exit.
2. In a project that has no IEDs, right-click the bay and select Import... to insert
the IED from a .pcmi file.
3. Right-click the IED and select Change SCL Version and IEC 61850 Edition
1 or IEC 61850 Edition 2.
The Change SCL Version dialog opens.
4. Click Yes to confirm the edition change.
Changing SCL Version dialog opens and shows the conversion progress.
When the conversion is complete, the Change SCL Version dialog opens.
5. Close the dialog by clicking OK.
6. Right-click the IED and select Export... to save the converted IED in a .pcmi
file.
4.7 Inserting an IED
SEMOD58416-5 v12
The context menu or the Object Types view shows the available IEDs possible to
insert on the bay level in the plant structure according to the installed connectivity
package.
On the bay level in the plant structure it is possible to:
Insert an IED in Online mode or in Offline mode :
Online mode: when the IED is already connected to PCM600 and the
communication is established, PCM600 can read the configuration
directly from the physical IED. This is useful when an order-specific
IED is used. The order configuration is written to the IED at the factory,
and can be accessed by PCM600. The housing type, the used overlay
Section 4 1MRK 511 398-UEN C
Setting up a project
48 670 series 2.2 IEC
Engineering manual