Because IEC 61850 edition 1 and IEC 61850 edition 2 templates
are incompatible, convert an IEC 61850 edition 1 template to IEC
61850 edition 2 before you insert it.
It is possible to give the inserted IED in the plant structure a user-
defined name. Be sure to only user characters a-z, A-Z, 0-9 and _.
Do not use space character in IED names.
4.7.1 Setting IED IP address in the project
GUID-4C451305-E268-49D8-B237-4EDFAFF6E322 v8
There are two alternatives to set the IP address of the IED object in PCM600. The
IED object in PCM600 must have the same IP address and subnetwork mask as the
front or rear port on the physical IED to which the PC is connected.
• Via the first window of the wizard when including a new IED in a project, see
Figure 27.
IEC09000713 V2 EN-US
Figure 27: Alternative 1: IP address via the first Wizard window
• Via the IP address property of the IED in the Object Properties window, see
Figure 28.
1MRK 511 398-UEN C Section 4
Setting up a project
670 series 2.2 IEC 57
Engineering manual