Column Description Read only
Subnetwork Shows the SCL subnetwork to which the access point is
connected, can be changed. This column shows the SCL
subnetworks available in the PCM600 project. SCL subnetworks
can be created/deleted in Subnetworks tab of IEC 61850
Configuration tool in PCM600.
When saving the ECT configuration after
selecting a subnetwork, ECT creates the
access point in the SCL model, unselecting
the subnetwork removes the access point
from the SCL model.
For IEC 61850 Ed2 IEDs this column will be
editable and for IEC 61850 Ed1 IEDs, this
column will not be editable because in
IEC 61850 Ed1 only one access point can
be modelled SCL.
No
IP Address Shows the IP address for the access point.
IP address of each access point should be in
different subnetworks that is defined by the
subnetwork mask.
Yes
Subnetwork mask Shows the Subnet mask of the access point. No
Default gateway Shows the Default gateway of the access point.
The Default Gateway address should be
within the subnetwork of the access point
that is defined by the subnetwork mask.
No
PCM600 access Enable/Disable PCM600 communication on an access point. No
MMS Enable/Disable IEC 61850 MMS communication on an access
point.
No
GOOSE Enable/Disable IEC 61850 GOOSE communication on an
access point.
No
DNP 3.0 Enable/Disable DNP 3.0 protocol on an access point. No
FTP Enable/Disable File Transfer Protocol on an access point. No
FST access Enable/Disable Field Service Tool access on an access point. No
SNTP Server Enable/Disable SNTP server communication on an access
point.
No
PTP(IEEE 1588) Precision Time protocol on an access point. No
PTP VLAN tag PTP VLAN identifier. No
The columns that are updated during a partial write are highlighted
when holding the pointer over the partial write button. The
highlighted columns will be written to the IED but not
synchronized towards SCL.
1MRK 511 398-UEN C Section 5
Ethernet configuration tool
670 series 2.2 IEC 61
Engineering manual