Loading...
IEC08000399.vsd
R
Y
G
R
Y
G
S
i
g
n
a
l
s
L
E
D
Ack
= Steady = FlashIllumination =>
IEC08000399 V1 EN-US
Figure 55: LHMI LED operation mode LatchedAck-F-S Prio / 2
LED operation mode LatchedAck-S-F
The LatchedAck-S-F mode operates in a similar manner as the LatchedAck-F-S
mode. However, on receiving a binary On signal, the LED enters a steady lit state.
When acknowledged and the signal remains On, it starts flashing.
LED operation mode LatchedColl-S
IEC08000402.vsd
= Steady = FlashIllumination =>
R
Y
G
R
Y
G
S
i
g
n
a
l
s
L
E
D
Reset LED
IEC08000402 V1 EN-US
Figure 56: LHMI: LED operation mode LatchedColl-S
A LED operating in the LatchedColl-S mode enters a steady lit state on receiving a
binary On signal. The LED remains lit even if the signal immediately transitions to
Off (pulse). When acknowledged, the LED is switched off, unless the attached
signal remains On. SeeFigure 56 for details.
1MRK 511 398-UEN C Section 7
Local HMI engineering
670 series 2.2 IEC 91
Engineering manual

Table of Contents