Table 700: Outputs and their values when activated
Name of OUTx Type Description Value when activated Value when
deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0
The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16) are active
equals 65535. This is the highest integer that can be converted to boolean by the ITBGAPC
function block.
The operator position input (PSTO) determines the operator place. The integer number that is
communicated to the ITBGAPC can only be written to the block while the PSTO is in position
“Remote”. If PSTO is in position ”Off” or ”Local”, then no changes are applied to the outputs.
15.13.7 Technical data
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v1
Table 701: Number of ITBGAPC instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
ITBGAPC 4 4 8
15.14 Pulse integrator TIGAPC
GUID-A01AA9D8-6030-4A16-A671-CC2D8E739D58 v3
1MRK 502 066-UUS B Section 15
Logic
995
Technical manual