15.14.1 Identification
GUID-C565D235-A935-4405-839D-AAF98E6CB85F v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse integrator TIGAPC
15.14.2 Functionality
GUID-FF3CBB22-0089-4BA0-BFE3-FD0E5BA96490 v2
The integrator function TIGAPC integrates input pulses and compares the integrated time with a
settable time delay to operate. Moreover, the time delay to reset the output is settable in this
function.
15.14.3 Function block
GUID-045C2E7A-B8B9-479D-8BAF-055E89E5270A v3
TIGAPC
IN OUT
ANSI14000062-1-en.vsd
ANSI14000062 V1 EN-US
Figure 518: TIGAPC function block
15.14.4 Signals
PID-3497-INPUTSIGNALS v7
Table 702: TIGAPC Input signals
Name Type Default Description
IN BOOLEAN 0 Input to integrator
PID-3497-OUTPUTSIGNALS v7
Table 703: TIGAPC Output signals
Name Type Description
OUT BOOLEAN Output from integrator
15.14.5 Settings
PID-3497-SETTINGS v7
Table 704: TIGAPC Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
tDelay 0.000 - 600.000 s 0.001 1.000 Time delay to operate
tReset 0.000 - 600.000 s 0.001 1.000 Time delay to reset