15.15.2 Functionality
GUID-390D7433-0C1C-48B4-9A90-71AA148C3C35 v3
Elapsed Time Integrator (TEIGAPC) function is a function that accumulates the elapsed time when
a given binary signal has been high, see also Figure
523.
Time Integration
with Retain
BLOCK
ACCTIME
RESET
IN
tWarning
tAlarm
OVERFLOW
WARNING
ALARM
q
-1
a>b
a
b
a>b
a
b
a>b
a
b
AND
AND
AND
q
-1
= unit delay
IEC13000290-2-en.vsd
999 999 s
IEC13000290 V2 EN-US
Figure 523: TEIGAPC logics
The main features of TEIGAPC
Applicable to long time integration up to 999 999.9 seconds
Supervision of overflow
Possibility to define a warning and an alarm with the resolution of 10 milliseconds
Retain the integration value
Possibilities for blocking and reset of the total integrated time
Report of the integrated time
15.15.3 Function block
GUID-6D50A060-7751-405B-AEC1-FAE942EBDA64 v2
TEIGAPC
BLOCK
IN
RESET
WARNING
ALARM
OVERFLOW
ACCTIME
IEC14000014-1-en.vsd
IEC14000014 V1 EN-US
Figure 524: TEIGAPC function block
15.15.4 Signals
PID-4047-INPUTSIGNALS v5
Table 707: TEIGAPC Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Freeze the integration and block the other outputs
IN BOOLEAN 0 The input signal that is used to measure the elapsed time, when
its value is high
RESET BOOLEAN 0 Reset the integration time
1MRK 502 066-UUS B Section 15
Logic
999
Technical manual