Time Integration
Transgression Supervision
Plus Retain
BLOCK
ACCTIME
RESET
IN
tAlarm
OVERFLOW
WARNING
ALARM
IEC12000195-3-en.vsd
Loop Delay
Loop Delay
tWarning
IEC12000195 V3 EN-US
Figure 525: TEIGAPC Simplified logic
TEIGAPC main functionalities
integration of the elapsed time when IN has been high
applicable to long time integration (≤999 999.9 seconds)
output ACCTIME presents integrated value in seconds
integrated value is retained in nonvolatile memory
any retained value with a warning/alarm/overflow is used as initiation value for the
integration following by a restart
RESET: Reset of the integration value. Consequently all other outputs are also reset
unconditionally on the input IN value
reset the value of the nonvolatile memory to zero
BLOCK: Freeze the integration and block/reset the other outputs
unconditionally on the signal value
BLOCK request overrides RESET request
Monitor and report the conditions of limit transgression
overflow if output ACCTIME >999999.9 seconds
alarm if ACCTIME >
tAlarm
warning if ACCTIME >
tWarning
The ACCTIME output represents the integrated time in seconds while
tOverflow
,
tAlarm
and
tWarning
are the time limit parameters in seconds.
tAlarm
and
tWarning
are user settable limits. They are also independent, that is, there is no check
if
tAlarm
>
tWarning
.
tAlarm
and
tWarning
are possible to be defined with a resolution of 10 ms, depending on the level
of the defined values for the parameters.
The limit for the overflow supervision is fixed at 999999.9 seconds. The outputs freeze if an
overflow occurs.
1MRK 502 066-UUS B Section 15
Logic
1001
Technical manual