15.16.5 Signals
PID-6503-INPUTSIGNALS v5
Table 712: INTCOMP Input signals
Name Type Default Description
INPUT INTEGER 0 Input value to be compared with reference value
REF INTEGER 0 Reference value to be compared with input value
PID-6503-OUTPUTSIGNALS v5
Table 713: INTCOMP Output signals
Name Type Description
INEQUAL BOOLEAN Input value is equal to the reference value
INHIGH BOOLEAN Input value is higher than the reference value
INLOW BOOLEAN Input value is lower than the reference value
15.16.6 Settings
PID-6503-SETTINGS v5
Table 714: INTCOMP Group settings (basic)
Name Values (Range) Unit Step Default Description
EnaAbs Signed
Absolute
- - Signed Selection for absolute or signed
comparison
RefSource Set Value
Input REF
- - Set Value Selection for reference value either input
or setting
SetValue -2000000000 -
2000000000
- 1 100 Set value for reference
15.17 Comparator for real inputs - REALCOMP
15.17.1 Identification
GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparator for real inputs REALCOMP Real<=>
15.17.2 Functionality
GUID-E17A88D7-D095-4F36-9CD5-64EBFD2A1DEA v1
The function gives the possibility to monitor the level of real value signals in the system relative to
each other or to a fixed value. It is a basic arithmetic function that can be used for monitoring,
supervision, interlocking and other logics.