PID-3584-OUTPUTSIGNALS v6
Table 721: CVMMXN Output signals
Name Type Description
S REAL Apparent Power magnitude of deadband value
S_RANGE INTEGER Apparent Power range
P_INST REAL Active Power
P REAL Active Power magnitude of deadband value
P_RANGE INTEGER Active Power range
Q_INST REAL Reactive Power
Q REAL Reactive Power magnitude of deadband value
Q_RANGE INTEGER Reactive Power range
PF REAL Power Factor magnitude of deadband value
PF_RANGE INTEGER Power Factor range
ILAG BOOLEAN Current is lagging voltage
ILEAD BOOLEAN Current is leading voltage
V REAL Calculated voltage magnitude of deadband value
V_RANGE INTEGER Calculated voltage range
I REAL Calculated current magnitude of deadband value
I_RANGE INTEGER Calculated current range
F REAL System frequency magnitude of deadband value
F_RANGE INTEGER System frequency range
PID-3760-INPUTSIGNALS v5
Table 722: CMMXU Input signals
Name Type Default Description
I3P GROUP
SIGNAL
- Group signal for current input
PID-3760-OUTPUTSIGNALS v6
Table 723: CMMXU Output signals
Name Type Description
IA REAL Phase A current magnitude of reported value
IA_RANGE INTEGER Phase A current magnitude range
IA_ANGL REAL Phase A current magnitude angle
IB REAL Phase B current magnitude of reported value
IB_RANGE INTEGER Phase B current magnitude range
IB_ANGL REAL Phase B current magnitude angle
IC REAL Phase C current magnitude of reported value
IC_RANGE INTEGER Phase C current magnitude range
IC_ANGL REAL Phase C current magnitude angle
1MRK 502 066-UUS B Section 16
Monitoring
1013
Technical manual