Name Values (Range) Unit Step Default Description
IMax 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
FrMin 0.000 - 100.000 Hz 0.001 0.000 Minimum value
FrMax 0.000 - 100.000 Hz 0.001 70.000 Maximum value
FrRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Mode A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
- - A, B, C Selection of measured current and voltage
PowMagFact 0.000 - 6.000 - 0.001 1.000 Magnitude factor to scale power
calculations
PowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shift
between measured I & V
k 0.000 - 1.000 - 0.001 0.000 Low pass filter coefficient for power
measurement, V and I
Table 733: CVMMXN Non group settings (advanced)
Name Values (Range) Unit Step Default Description
SDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
SZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0.001% of range
SHiHiLim 0.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
SHiLim 0.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
SLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
PDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
PZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0.001% of range
PHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
PHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
PLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase
PLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase
PLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
Table continues on next page
1MRK 502 066-UUS B Section 16
Monitoring
1017
Technical manual