Name Values (Range) Unit Step Default Description
FrLowLowLim 0.000 - 100.000 Hz 0.001 45.000 Low Low limit (physical value)
FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
VGenZeroDb 1 - 100 %VB 1 5 Zero point clamping in % of UBase
IGenZeroDb 1 - 100 %IB 1 5 Zero point clamping in % of IBase
VMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at
5% of Vn
VMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at
30% of Vn
VMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at
100% of Vn
IMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at
5% of In
IMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at
30% of In
IMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at
100% of In
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of In
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of In
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of In
PID-3760-SETTINGS v6
Table 734: CMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
IA_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
IA_Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IA_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
IA_AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IB_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IB_Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IB_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IB_AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IC_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table continues on next page
1MRK 502 066-UUS B Section 16
Monitoring
1019
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals