Name Values (Range) Unit Step Default Description
IC_Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IC_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IC_AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table 735: CMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
IA_ZeroDb 0 - 100000 m% 1 1 Zero point clamping
IA_HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IA_HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at
5% of In
IMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at
30% of In
IA_LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IA_LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at
100% of In
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of In
IA_Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of In
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of In
IA_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
IB_ZeroDb 0 - 100000 m% 1 1 Zero point clamping
IB_HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IB_HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IB_LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IB_LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IB_Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IB_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
IC_ZeroDb 0 - 100000 m% 1 1 Zero point clamping
IC_HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IC_HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IC_LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IC_LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IC_Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IC_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits