PID-3767-SETTINGS v5
Table 736: VMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
VAB_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
VAB_ZeroDb 0 - 100000 m% 1 1 Zero point clamping
VAB_Max 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of VBase
VAB_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
VAB_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VBC_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VB_ZeroDb 0 - 100000 m% 1 1 Zero point clamping
VBC_Max 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of VBase
VBC_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VBC_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VCA_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VC_ZeroDb 0 - 100000 m% 1 1 Zero point clamping
VCA_Max 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of VBase
VCA_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VCA_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table 737: VMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
VAB_HiHiLim 0.0 - 200.0 %VB 0.1 150.0 High High limit in % of UBase
VAB_HiLim 0.0 - 200.0 %VB 0.1 120.0 High limit in % of VBase
VAB_LowLim 0.0 - 200.0 %VB 0.1 80.0 Low limit in % of VBase
VAB_LowLowLim 0.0 - 200.0 %VB 0.1 60.0 Low Low limit in % of VBase
VMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at
100% of Vn
VAB_Min 0.0 - 200.0 %VB 0.1 50.0 Minimum value in in % of VBase
VAB_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
Table continues on next page