Name Values (Range) Unit Step Default Description
VBC_HiHiLim 0.0 - 200.0 %VB 0.1 150.0 High High limit in % of UBase
VBC_HiLim 0.0 - 200.0 %VB 0.1 120.0 High limit in % of VBase
VBC_LowLim 0.0 - 200.0 %VB 0.1 80.0 Low limit in % of VBase
VBC_LowLowLim 0.0 - 200.0 %VB 0.1 60.0 Low Low limit in % of VBase
VBC_Min 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of VBase
VBC_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
VCA_HiHiLim 0.0 - 200.0 %VB 0.1 150.0 High High limit in % of UBase
VCA_HiLim 0.0 - 200.0 %VB 0.1 120.0 High limit in % of VBase
VCA_LowLim 0.0 - 200.0 %VB 0.1 80.0 Low limit in % of VBase
VCA_LowLowLim 0.0 - 200.0 %VB 0.1 60.0 Low Low limit in % of VBase
VCA_Min 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of VBase
VCA_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
PID-3723-SETTINGS v2
Table 738: CMSQI Non group settings (basic)
Name Values (Range) Unit Step Default Description
3I0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
3I0ZeroDb 0 - 100000 m% 1 1 Zero point clamping
3I0Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
3I0Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
3I0RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
3I0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
3I0AngMin -180.000 -
180.000
Deg 0.001 -180.000 Minimum value
3I0AngMax -180.000 -
180.000
Deg 0.001 180.000 Maximum value
3I0AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
I1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
I1ZeroDb 0 - 100000 m% 1 1 Zero point clamping
Table continues on next page