Name Values (Range) Unit Step Default Description
I1AngMin -180.000 -
180.000
Deg 0.001 -180.000 Minimum value
I2HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
I2HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
I2LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
I2LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
I2AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
I2AngMax -180.000 -
180.000
Deg 0.001 180.000 Maximum value
PID-3725-SETTINGS v3
Table 740: VMSQI Non group settings (basic)
Name Values (Range) Unit Step Default Description
3V0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
3V0ZeroDb 0 - 100000 m% 1 1 Zero point clamping
3V0Min 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of VBase
3V0Max 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of VBase
3V0RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
3V0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
3V0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
3V0AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
3V0AngMin -180.000 -
180.000
Deg 0.001 -180.000 Minimum value
3V0AngMax -180.000 -
180.000
Deg 0.001 180.000 Maximum value
3V0AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
V1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V1ZeroDb 0 - 100000 m% 1 1 Zero point clamping
V1Min 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of VBase
V1Max 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of VBase
V1RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Table continues on next page
Section 16 1MRK 502 066-UUS B
Monitoring
1024
Technical manual