Name Values (Range) Unit Step Default Description
V1AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
V2HiHiLim 0.0 - 200.0 %VB 0.1 150.0 High High limit in % of UBase
V2HiLim 0.0 - 200.0 %VB 0.1 120.0 High limit in % of VBase
V2LowLim 0.0 - 200.0 %VB 0.1 80.0 Low limit in % of VBase
V2LowLowLim 0.0 - 200.0 %VB 0.1 60.0 Low Low limit in % of VBase
V2AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
PID-3756-SETTINGS v5
Table 742: VNMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
VA_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
VA_ZeroDb 0 - 100000 m% 1 1 Zero point clamping
VA_Max 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of VBase
VA_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
VA_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
VA_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VB_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VB_ZeroDb 0 - 100000 m% 1 1 Zero point clamping
VB_Max 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of VBase
VB_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VB_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
VB_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VC_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VC_ZeroDb 0 - 100000 m% 1 1 Zero point clamping
VC_Max 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of VBase
Table continues on next page