The voltages (phase or phase-phase voltage, magnitude and angle) are available on the outputs
and each magnitude output has a corresponding supervision level output (Vxy_RANG). The
supervision output signal is an integer in the interval 0-4, see section "Measurement supervision".
16.1.7.5 Voltage and current sequence measurements VMSQI, CMSQI
SEMOD54417-299 v6
The measurement functions must be connected to three-phase current (CMSQI) or voltage
(VMSQI) input in the configuration tool to be operable. No outputs, other than X_RANG, are
calculated within the measuring blocks and it is not possible to calibrate the signals. Input signals
are obtained from the pre-processing block and transferred to corresponding output.
Positive, negative and three times zero sequence quantities are available on the outputs (voltage
and current, magnitude and angle). Each magnitude output has a corresponding supervision level
output (X_RANGE). The output signal is an integer in the interval 0-4, see section
"Measurement
supervision".
16.1.8 Technical data
M12386-1 v14.1.1
Table 750: CVMMXN technical data
Function Range or value Accuracy
Frequency (0.95-1.05) x f
n
±2.0 mHz
Voltage (10 to 300) V
±0.3% of V at V≤ 50 V
±0.2% of V at V> 50 V
Current (0.1-4.0) x I
n
±0.8% of I at 0.1 x I
n
< I < 0.2 x I
n
± 0.5% of I at 0.2 x I
n
< I < 0.5 x I
n
±0.2% of I at 0.5 x I
n
< I < 4.0 x I
n
Active power, P (10 to 300) V
(0.1-4.0) x I
n
±0.5% of S
n
at S ≤0.5 x S
n
±0.5% of S at S > 0.5 x S
n
(100 to 220) V
(0.5-2.0) x I
n
cos φ> 0.7
±0.2% of P
Reactive power, Q (10 to 300) V
(0.1-4.0) x I
n
±0.5% of S
n
at S ≤0.5 x S
n
±0.5% of S at S > 0.5 x S
n
(100 to 220) V
(0.5-2.0) x I
n
cos φ< 0.7
±0.2% of Q
Apparent power, S (10 to 300) V
(0.1-4.0) x I
n
±0.5% of S
n
at S ≤0.5 x S
n
±0.5% of S at S >0.5 x S
n
(100 to 220) V
(0.5-2.0) x I
n
±0.2% of S
Power factor, cos (φ)
(10 to 300) V
(0.1-4.0) x I
n
<0.02
(100 to 220) V
(0.5-2.0) x I
n
<0.01
Section 16 1MRK 502 066-UUS B
Monitoring
1040
Technical manual