Name Values (Range) Unit Step Default Description
UnderTrigLe09 0 - 200 % 1 50 Under trigger level for analog channel 9 in
% of signal
OverTrigOp09 Disabled
Enabled
- - Disabled Use over level trigger for analog channel 9
(on) or not (off)
OverTrigLe09 0 - 5000 % 1 200 Over trigger level for analog channel 9 in %
of signal
NomValue10 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 10
UnderTrigOp10 Disabled
Enabled
- - Disabled Use under level trigger for analog channel
10 (on) or not (off)
UnderTrigLe10 0 - 200 % 1 50 Under trigger level for analog channel 10 in
% of signal
OverTrigOp10 Disabled
Enabled
- - Disabled Use over level trigger for analog channel 10
(on) or not (off)
OverTrigLe10 0 - 5000 % 1 200 Over trigger level for analog channel 10 in
% of signal
GUID-E05EEC82-CB90-4E73-B9C9-4C16FD95FCBF v1
A2RADR to A4RADR functions have the same Non group settings (basic) as A1RADR but with
different numbering:
A2RADR: Operation11 to Operation20
A3RADR: Operation21 to Operation30
A4RADR: Operation31 to Operation40
A2RADR to A4RADR functions have the same Non group settings (advanced) as A1RADR but with
different numbering (examples given in brackets):
A2RADR: 11 to 20 (NomValue11, nominal value for analog channel 11)
A3RADR: 21 to 30 (NomValue21, nominal value for analog channel 21)
A4RADR: 31 to 40 (NomValue31, nominal value for analog channel 31)
PID-3798-SETTINGS v4
Table 779: B1RBDR Non group settings (basic)
Name Values (Range) Unit Step Default Description
TrigDR01 Disabled
Enabled
- - Disabled Trigger operation On/Off
SetLED01 Disabled
Pickup
Trip
Pickup and Trip
- - Disabled Set LED on HMI for binary channel 1
TrigDR02 Disabled
Enabled
- - Disabled Trigger operation On/Off
SetLED02 Disabled
Pickup
Trip
Pickup and Trip
- - Disabled Set LED on HMI for binary channel 2
TrigDR03 Disabled
Enabled
- - Disabled Trigger operation On/Off
Table continues on next page
Section 16 1MRK 502 066-UUS B
Monitoring
1072
Technical manual