16.10.4 Signals
PID-6998-INPUTSIGNALS v1
Table 794: TEILGAPC Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Freeze the accumulation and block the outputs
IN BOOLEAN 0 The input signal that is used to measure the elapsed time, when
its value is high
ADDTIME BOOLEAN 0 Add time to the accumulation
RESET BOOLEAN 0 Reset accumulated time
PID-6998-OUTPUTSIGNALS v1
Table 795: TEILGAPC Output signals
Name Type Description
ALARM BOOLEAN Indicator that accumulated time has reached alarm limit
WARNING BOOLEAN Indicator that accumulated time has reached warning limit
OVERFLOW BOOLEAN Indicator that accumulated time has reached overflow limit
ACC_HOUR REAL Accumulated time in hours
ACC_DAY REAL Accumulated time in days
16.10.5 Settings
PID-6998-SETTINGS v1
Table 796: TEILGAPC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
tAlarm 1.0 - 99999.9 Hour 0.1 90000.0 Time limit for alarm supervision
tWarning 1.0 - 99999.9 Hour 0.1 50000.0 Time limit for warning supervision
tAddToTime 0.0 - 99999.9 Hour 0.1 0.0 Time to add to the accumulation
16.10.6 Operation principle
GUID-C7F91D4E-5942-4006-B7C8-4F499E7DC49D v3
Figure 573 describes the simplified logic of the function.