Time Accumulation
Transgression Supervision
Plus Retain
BLOCK
ACC_HOUR
RESET
IN
tAlarm
OVERFLOW
WARNING
ALARM
IEC15000322.vsd
Loop Delay
Loop Delay
tWarning
ACC_DAY
ADDTIME
tAddToTime
IEC15000322 V1 EN-US
Figure 573: TEILGAPC Simplified logic
TEILGAPC main functionalities
IN: Accumulation of the elapsed time when input IN is high
applicable to very long time accumulation (≤
99999.9
hours)
output
ACC_HOUR
presents accumulated value in hours and
ACC_DAY
presents
accumulated value in days
accumulated value is retained in a non-volatile memory
any retained value is used as initiation value for the integration following by a restart
RESET: Reset of the accumulated value. Consequently all other outputs are also reset
independent of the input
IN
value
reset the value of the nonvolatile memory to zero.
Note that the nonvolatile memory will not reset to zero if the input
IN
is high during the
reset.
reset can be made by activation of input
RESET
or from LHMI or with IEC 61850
command
ADDTIME: Manually add time to the currently accumulated time
the amount of time to be added is defined by a setting
tAddToTime
time is added through activation of input
ADDTIME
or from LHMI or with IEC 61850
command
BLOCK: Freeze the accumulation and block/reset the other outputs
independent of the input
IN
value
BLOCK
request overrides
RESET
request
Monitor and report the conditions of limit transgression
overflow if output
ACC_HOUR
>
99 999.9
hours
alarm if output
ACC_HOUR
>
tAlarm
warning if output
ACC_HOUR
>
tWarning
1MRK 502 066-UUS B Section 16
Monitoring
1099
Technical manual