Function block SPA address
MIM15-CH6 4-O-6747
MIM16-CH1 4-O-6755
MIM16-CH2 4-O-6758
MIM16-CH3 4-O-6759
MIM16-CH4 4-O-6762
MIM16-CH5 4-O-6763
MIM16-CH6 4-O-6766
The SPA addresses for the pulse counter values PCFCNT:1 to PCFCNT:16 are found in table 856.
Table 856: SPA addresses for the PCFCNT function
Function block SPA address CNT_VAL SPA address NEW_VAL
PCFCNT:1 6-O-2788 6-O-2787
PCFCNT:2 6-O-2794 6-O-2793
PCFCNT:3 6-O-2800 6-O-2799
PCFCNT:4 6-O-2806 6-O-2805
PCFCNT:5 6-O-2812 6-O-2811
PCFCNT:6 6-O-2818 6-O-2817
PCFCNT:7 6-O-2824 6-O-2823
PCFCNT:8 6-O-2830 6-O-2829
PCFCNT:9 6-O-2836 6-O-2835
PCFCNT:10 6-O-2842 6-O-2841
PCFCNT:11 6-O-2848 6-O-2847
PCFCNT:12 6-O-2854 6-O-2853
PCFCNT:13 6-O-2860 6-O-2859
PCFCNT:14 6-O-2866 6-O-2865
PCFCNT:15 6-O-2872 6-O-2871
PCFCNT:16 6-O-2878 6-O-2877
I/O modules
M11880-16 v4
To read binary inputs, the SPA-addresses for the outputs of the I/O-module function block are
used, that is, the addresses for BI1 – BI16. For SPA addresses, refer to section Related documents
in Product Guide.
M11880-35 v1
Single command, 16 signals
M11880-51 v4
The IEDs can be provided with a function to receive signals either from a substation automation
system or from the local HMI. That receiving function block has 16 outputs that can be used, for
example, to control high voltage apparatuses in switchyards. For local control functions, the local
HMI can also be used.
Single command, 16 signals function consists of three function blocks; SINGLECMD:1 to
SINGLECMD:3 for 16 binary output signals each.
Section 18 1MRK 502 066-UUS B
Station communication
1156
Technical manual