Table 892: I103IEDCMD supported indications
INF Description
19 LED Reset
23 Activate setting group 1
24 Activate setting group 2
25 Activate setting group 3
26 Activate setting group 4
Function commands in control direction, pre-defined I103CMD
M11874-53 v6
Function command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter
FunctionType
.
Information number is defined for each output signals.
Table 893: Pre-defined I103CMD supported indications
INF Description
16 Auto-recloser on/off
17 Teleprotection on/off
18 Protection on/off
Function commands in control direction, user-defined, I103USRCMD
M11874-72 v5
Function command blocks in control direction with user-defined output signals.
Number of instances: 4
Function type for each function block instance in private range is selected with parameter
FunctionType
.
Information number must be selected for each output signal. Default values are 1 - 8.
Table 894: I103USRCMD supported indications
INF Description
1
1)
Output signal 01
2* Output signal 02
3* Output signal 03
4* Output signal 04
5* Output signal 05
6* Output signal 06
7* Output signal 07
8* Output signal 08
1) * User defined information number
1MRK 502 066-UUS B Section 18
Station communication
1183
Technical manual