Status
M11874-107 v1
Terminal status indications in monitor direction, I103IED
M11874-109 v7
Indication block for status in monitor direction with defined IED functions.
Number of instances: 1
Function type is selected with parameter
FunctionType
.
Information number is defined for each input signals.
Table 895: I103IED supported functions
INF Description
19 LED reset
21 TestMode
22 Local Parameter setting
23 Setting group 1 active
24 Setting group 2 active
25 Setting group 3 active
26 Setting group 4 active
Function status indications in monitor direction, user-defined, I103USRDEF
M11874-137 v7
Function indication block in monitor direction with user-defined input signals.
Number of instances: 20
Function type is selected with parameter
FunctionType
.
Information number is required for each input signal.
Table 896: I103USRDEF Information number default values
INF Description GI TYP COT
1
1)
Input signal 01 x/- 1/2 1,7,(9)
2* Input signal 02 x/- 1/2 1,7,(9)
3* Input signal 03 x/- 1/2 1,7,(9)
4* Input signal 04 x/- 1/2 1,7,(9)
5* Input signal 05 x/- 1/2 1,7,(9)
6* Input signal 06 x/- 1/2 1,7,(9)
7* Input signal 07 x/- 1/2 1,7,(9)
8* Input signal 08 x/- 1/2 1,7,(9)
1) * User defined information number
Supervision indications in monitor direction, I103SUPERV
M11874-171 v7
Indication block for supervision in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter
FunctionType
.
Section 18 1MRK 502 066-UUS B
Station communication
1184
Technical manual