INF FUN GI TYP COT Description
* * No, polled
with CL2
* 2,7 Meas4
* * No, polled
with CL2
* 2,7 Meas5
* * No, polled
with CL2
* 2,7 Meas6
* * No, polled
with CL2
* 2,7 Meas7
* * No, polled
with CL2
* 2,7 Meas8
* * No, polled
with CL2
* 2,7 Meas9
1) * User defined information value (PARAM.3)
2) * User defined information value (PARAM.2)
3) 9 = Measurands II, Format = Measurand II (7.3.1.8 in IEC 60870-5-103:1997), semantics per IE is defined by
semantics of connected source.
<Number of information elements> is defined by index of first input not connected.
Example: Input1, Input2, and Input4 are connected, Input3 is not connected.
<Number of information elements> will be 3 (Input3 NOT connected) -1 = 2, that is, only Input1 and
Input2 will be transmitted.
Disturbance recordings
M11874-467 v6
The following elements are used in the ASDUs (Application Service Data Units) defined in the
standard.
Analog signals, 40-channels: the channel number for each channel has to be specified. Channels
used in the public range are 1 to 8 and with:
I
A
connected to channel 1 on disturbance function block A1RADR
I
B
connected to channel 2 on disturbance function block A1RADR
I
C
connected to channel 3 on disturbance function block A1RADR
I
N
connected to channel 4 on disturbance function block A1RADR
V
AE
connected to channel 5 on disturbance function block A1RADR
V
BE
connected to channel 6 on disturbance function block A1RADR
V
CE
connected to channel 7 on disturbance function block A1RADR
V
EN
connected to channel 8 on disturbance function block A1RADR
Channel number used for the remaining 32 analog signals are numbers in the private range 64 to
95.
Binary signals, 96-channels: for each channel the user can specify a FUNCTION TYPE and an
INFORMATION NUMBER.
M11874-629 v7
Disturbance upload
All analog and binary signals that are recorded with disturbance recorder can be reported to the
master. The last eight disturbances that are recorded are available for transfer to the master. A
Section 18 1MRK 502 066-UUS B
Station communication
1188