Data Value Data Valid Comm Valid Test
Receiver in block 0 0 1 0
Receiver in block and communication
error
0 0 0 0
Receiver in test mode and incoming data
with q= Normal
Updated 1 1 0
Receiver in test mode and incoming data
with q= Test
Updated 1 1 1
Communication Error 0 0 0 0
At least one of the inputs of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if easy GOOSE
engineering is enabled) to receive any data. Only those outputs whose source input
is linked/connected will be updated.
The implementation for IEC 61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the APPxVAL output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the APPxVAL output will be LOW.
1MRK 502 066-UUS B Section 18
Station communication
1195
Technical manual